Cast Resin Dry Type Transformer (100 – 3,150 kVA, up to 36 kV)

Three-phase cast resin dry type transformers from 100 to 3,150 kVA for system voltages to 36 kV. No liquid of any kind, so no bund, no leak risk and no oil sampling. Specified wherever a transformer sits inside an occupied building.
Protection IP33

Where a transformer has to go indoors — a basement plant room, a data hall, a hospital, an airport terminal, a shopping centre, a metro station — the fire strategy and the insurer usually rule out oil. A cast resin unit answers that: the windings are encapsulated in epoxy under vacuum, there is no liquid in the machine at all, and the resin system is non-flammable and self-extinguishing.

Specification we quote to

  • 100 to 3,150 kVA, three phase, 50 Hz; larger ratings by enquiry
  • System voltage to 36 kV; 400 V or 433 V secondary
  • Windings vacuum cast in epoxy, voidless, slow cured to avoid cracking
  • Partial discharge measured and reported on every unit to BS EN IEC 60076-11
  • Quartz-filled or fibreglass-reinforced resin system
  • Insulation class F as standard, class H available
  • LV foil winding in aluminium or copper; HV flat or round wire
  • Non-flammable and self-extinguishing: no oil, no bund, no containment, no fluid sampling
  • IP00 open as standard; IP20, IP23 and IP33 enclosures available
  • Forced ventilation raises rated power by up to 40 per cent
  • PT100 sensors in the LV winding with temperature controller, alarm and trip
  • Anti-vibration pads and seismic restraint available for occupied buildings

Technical specification

Rated power 100 – 3,150 kVA; larger by enquiry
Highest voltage for equipment Up to 36 kV
HV voltage 11,000 V; 6,600 V and 33,000 V available
LV voltage 400 V or 433 V to client specification
Frequency 50 Hz
Vector group Dyn11 standard
Tappings Off-circuit links on HV, ±2 × 2.5%; on-load tap changer available
Impedance 6.0% typical, confirmed per rating
Windings LV aluminium or copper foil; HV flat or round wire, vacuum cast
Resin system Quartz-filled, or fibreglass-reinforced where short-circuit strength governs
Core Cold rolled grain-oriented silicon steel, resin coated and painted
Insulation class F standard; H available
Climatic, environmental and fire class C2, E2 and F1 to BS EN IEC 60076-11
Partial discharge Measured and reported per unit against the BS EN IEC 60076-11 limit
Losses Ecodesign Tier 2 maxima or better
Cooling AN standard; AF with fans for up to 40 per cent uplift
Enclosure IP00 open as standard; IP20 indoor, IP23 and IP33 indoor or outdoor
Protection PT100 per phase with temperature controller, alarm and trip contacts
Terminations HV and LV bars drilled to the client's cable lugs; cable box available with an enclosure
Options Anti-vibration pads, seismic restraint, enclosure heater, surge arresters, current transformers, interlocks
Standards BS EN IEC 60076-11, BS EN 50541-1, IEC 60076

Why vacuum casting matters

Resin poured at atmospheric pressure traps microscopic voids, and those voids ionise under electrical stress, grow, and eventually break down the insulation. Casting under vacuum eliminates them. The measure of success is partial discharge, which is reported on every unit against the limit in BS EN IEC 60076-11.

A dry type unit also occupies less floor area than an oil transformer of the same rating, so it can sit closer to the load centre and the LV cable run gets shorter. It needs no drying before re-energisation after a long shutdown, and individual coils can be replaced on site rather than returning the whole machine to a works.

Applications

  • Data centres and white space distribution
  • Hospitals, schools, airports and shopping centres
  • Basement and ground-floor plant rooms in occupied buildings
  • Metro, rail and tunnel installations
  • Refineries, offshore platforms and marine applications
  • EV charging hubs where a non-oil solution is specified

Compliance

Tier 2 minimum energy performance standards have applied to every new power transformer installation in Great Britain since 1 July 2021. Units are specified Ecodesign Tier 2 compliant and UKCA or CE marked, with no-load and load loss figures confirmed before order. Transformers intended for a network to be adopted by a distribution network operator fall outside this offer, as adoption requires that operator's own product approval.

Documentation

Each order is specified to include a routine test report to BS EN IEC 60076-11, a declaration of conformity, general arrangement and foundation drawings, a rating plate drawing and an operation and maintenance manual. Independent short-circuit type test certificates and witness testing can be requested at enquiry stage.

Lead time and enquiry

Indicative lead time is 8 to 14 weeks ex works, confirmed at order. Tell us the rating, the HV and LV voltages, the enclosure or IP rating, whether forced ventilation is needed, and your required on-site date, and we will come back with a price and guaranteed loss figures.

Need this product for your project? Our engineers help you choose the right model and prepare a quotation.