Where a transformer has to go indoors — a basement plant room, a data hall, a hospital, an airport terminal, a shopping centre, a metro station — the fire strategy and the insurer usually rule out oil. A cast resin unit answers that: the windings are encapsulated in epoxy under vacuum, there is no liquid in the machine at all, and the resin system is non-flammable and self-extinguishing.
Specification we quote to
Technical specification
| Rated power | 100 – 3,150 kVA; larger by enquiry |
| Highest voltage for equipment | Up to 36 kV |
| HV voltage | 11,000 V; 6,600 V and 33,000 V available |
| LV voltage | 400 V or 433 V to client specification |
| Frequency | 50 Hz |
| Vector group | Dyn11 standard |
| Tappings | Off-circuit links on HV, ±2 × 2.5%; on-load tap changer available |
| Impedance | 6.0% typical, confirmed per rating |
| Windings | LV aluminium or copper foil; HV flat or round wire, vacuum cast |
| Resin system | Quartz-filled, or fibreglass-reinforced where short-circuit strength governs |
| Core | Cold rolled grain-oriented silicon steel, resin coated and painted |
| Insulation class | F standard; H available |
| Climatic, environmental and fire class | C2, E2 and F1 to BS EN IEC 60076-11 |
| Partial discharge | Measured and reported per unit against the BS EN IEC 60076-11 limit |
| Losses | Ecodesign Tier 2 maxima or better |
| Cooling | AN standard; AF with fans for up to 40 per cent uplift |
| Enclosure | IP00 open as standard; IP20 indoor, IP23 and IP33 indoor or outdoor |
| Protection | PT100 per phase with temperature controller, alarm and trip contacts |
| Terminations | HV and LV bars drilled to the client's cable lugs; cable box available with an enclosure |
| Options | Anti-vibration pads, seismic restraint, enclosure heater, surge arresters, current transformers, interlocks |
| Standards | BS EN IEC 60076-11, BS EN 50541-1, IEC 60076 |
Why vacuum casting matters
Resin poured at atmospheric pressure traps microscopic voids, and those voids ionise under electrical stress, grow, and eventually break down the insulation. Casting under vacuum eliminates them. The measure of success is partial discharge, which is reported on every unit against the limit in BS EN IEC 60076-11.
A dry type unit also occupies less floor area than an oil transformer of the same rating, so it can sit closer to the load centre and the LV cable run gets shorter. It needs no drying before re-energisation after a long shutdown, and individual coils can be replaced on site rather than returning the whole machine to a works.
Applications
Compliance
Tier 2 minimum energy performance standards have applied to every new power transformer installation in Great Britain since 1 July 2021. Units are specified Ecodesign Tier 2 compliant and UKCA or CE marked, with no-load and load loss figures confirmed before order. Transformers intended for a network to be adopted by a distribution network operator fall outside this offer, as adoption requires that operator's own product approval.
Documentation
Each order is specified to include a routine test report to BS EN IEC 60076-11, a declaration of conformity, general arrangement and foundation drawings, a rating plate drawing and an operation and maintenance manual. Independent short-circuit type test certificates and witness testing can be requested at enquiry stage.
Lead time and enquiry
Indicative lead time is 8 to 14 weeks ex works, confirmed at order. Tell us the rating, the HV and LV voltages, the enclosure or IP rating, whether forced ventilation is needed, and your required on-site date, and we will come back with a price and guaranteed loss figures.
| Category | Cast Resin Dry Type Transformers |
|---|