Pulsar sources hermetically sealed distribution transformers for privately owned HV networks in the UK — industrial sites, commercial developments, campuses, water and rail infrastructure, and renewable generation. These are the units that sit behind the point of supply, where the network belongs to the site owner rather than the distribution network operator.
Specification we quote to
Technical specification
| Rated power | 25 – 2,500 kVA; larger ratings by enquiry |
| Highest voltage for equipment | Up to 36 kV |
| HV voltage | 11,000 V or 6,600 V, dual ratio available; 33,000 V by enquiry |
| LV voltage | 433 – 250 V at no load; 400 V to client specification |
| Frequency | 50 Hz |
| Vector group | Dyn11 standard; other groups available |
| Tappings | Off-circuit ±2 × 2.5% on HV; on-load tap changer available |
| Impedance | 4.75% up to 1,000 kVA, 6.0% above |
| Windings | Copper or aluminium |
| Core | Cold rolled grain-oriented silicon steel |
| Losses | Ecodesign Tier 2 maxima or better |
| Tank | Sealed corrugated wall, vacuum filled; conservator type available |
| Cooling | ONAN; ONAF available |
| Insulating fluid | Mineral oil to IEC 60296; natural or synthetic ester available |
| Temperature rise | 60 K top oil, 65 K winding |
| Insulation level | 28 / 75 kV at 12 kV; 50 / 125 kV at 24 kV; 70 / 170 kV at 36 kV |
| Protection | Pressure relief device and thermometer pocket; hermetic protection relay or Buchholz relay as specified |
| Terminations | HV porcelain or resin plug-in bushings, or separable connectors to EN 50180 and EN 50181; LV copper palms, air bushings or cable box to BS 2562 |
| Standards | BS EN 60076-1 to -5, BS EN 50588-1, IEC 60076 |
Applications
Compliance
Tier 2 minimum energy performance standards have applied to every new power transformer installation in Great Britain since 1 July 2021. Units are specified Ecodesign Tier 2 compliant and UKCA or CE marked, with no-load and load loss figures confirmed before order. Units built to ENA TS 35-1 can be quoted where a client specification calls for it. Transformers intended for a network to be adopted by a distribution network operator fall outside this offer, as adoption requires that operator's own product approval.
Documentation
Each order is specified to include a routine test report to BS EN 60076, a declaration of conformity, general arrangement and foundation drawings, a rating plate drawing and an operation and maintenance manual. Independent short-circuit type test certificates and witness testing can be requested at enquiry stage.
Lead time and enquiry
Indicative lead time is 8 to 14 weeks ex works, confirmed at order. Tell us the rating, the HV and LV voltages, the vector group and impedance, indoor or outdoor, and your required on-site date, and we will come back with a price and guaranteed loss figures.