Hermetically Sealed Distribution Transformer (25 – 2,500 kVA, up to 36 kV)

Three-phase hermetically sealed distribution transformers from 25 to 2,500 kVA for system voltages to 36 kV. No breather, no oil sampling, no routine maintenance. Built to BS EN 60076 and supplied Ecodesign Tier 2 compliant, with guaranteed loss figures declared before order.

Pulsar sources hermetically sealed distribution transformers for privately owned HV networks in the UK — industrial sites, commercial developments, campuses, water and rail infrastructure, and renewable generation. These are the units that sit behind the point of supply, where the network belongs to the site owner rather than the distribution network operator.

Specification we quote to

  • 25 to 2,500 kVA, three phase or single phase, 50 Hz
  • System voltage to 36 kV; 11,000 V and 6,600 V dual-ratio primaries available
  • 433 – 250 V secondary to UK practice, or 400 V to a client specification
  • Sealed corrugated tank, vacuum filled: no breather, no silica gel, no oil sampling regime
  • Hermetic protection relay available from 630 kVA upwards
  • Ecodesign Tier 2 loss levels, with guaranteed figures confirmed at quotation
  • Copper or aluminium windings; cold rolled grain-oriented core
  • Mineral oil to IEC 60296, or natural ester (FR3) where a fire-rated biodegradable fluid is required
  • Porcelain bushings, resin plug-in bushings, or a cable box to BS 2562
  • Two-pack epoxy finish, RAL and corrosion class to the project requirement

Technical specification

Rated power 25 – 2,500 kVA; larger ratings by enquiry
Highest voltage for equipment Up to 36 kV
HV voltage 11,000 V or 6,600 V, dual ratio available; 33,000 V by enquiry
LV voltage 433 – 250 V at no load; 400 V to client specification
Frequency 50 Hz
Vector group Dyn11 standard; other groups available
Tappings Off-circuit ±2 × 2.5% on HV; on-load tap changer available
Impedance 4.75% up to 1,000 kVA, 6.0% above
Windings Copper or aluminium
Core Cold rolled grain-oriented silicon steel
Losses Ecodesign Tier 2 maxima or better
Tank Sealed corrugated wall, vacuum filled; conservator type available
Cooling ONAN; ONAF available
Insulating fluid Mineral oil to IEC 60296; natural or synthetic ester available
Temperature rise 60 K top oil, 65 K winding
Insulation level 28 / 75 kV at 12 kV; 50 / 125 kV at 24 kV; 70 / 170 kV at 36 kV
Protection Pressure relief device and thermometer pocket; hermetic protection relay or Buchholz relay as specified
Terminations HV porcelain or resin plug-in bushings, or separable connectors to EN 50180 and EN 50181; LV copper palms, air bushings or cable box to BS 2562
Standards BS EN 60076-1 to -5, BS EN 50588-1, IEC 60076

Applications

  • Industrial and commercial private HV networks
  • Campus, estate, water, rail and port distribution
  • Solar and battery storage step-up duty
  • Package substation and switchgear manufacturers
  • Like-for-like replacement of an existing unit

Compliance

Tier 2 minimum energy performance standards have applied to every new power transformer installation in Great Britain since 1 July 2021. Units are specified Ecodesign Tier 2 compliant and UKCA or CE marked, with no-load and load loss figures confirmed before order. Units built to ENA TS 35-1 can be quoted where a client specification calls for it. Transformers intended for a network to be adopted by a distribution network operator fall outside this offer, as adoption requires that operator's own product approval.

Documentation

Each order is specified to include a routine test report to BS EN 60076, a declaration of conformity, general arrangement and foundation drawings, a rating plate drawing and an operation and maintenance manual. Independent short-circuit type test certificates and witness testing can be requested at enquiry stage.

Lead time and enquiry

Indicative lead time is 8 to 14 weeks ex works, confirmed at order. Tell us the rating, the HV and LV voltages, the vector group and impedance, indoor or outdoor, and your required on-site date, and we will come back with a price and guaranteed loss figures.